A convector or a radiator under the window

In brief: Short answer: if the glazing goes to the floor, there is nowhere to hang a radiator, and an in-floor convector in the screed works; and when the screed is already poured, a floor-standing FRH or a skirting BR. With an ordinary window with a sill, a radiator is simpler to install and no worse: the choice is dictated by geometry and the coolant mode, not by “which is better in general”.

Both devices give the room the heat of the water from the circuit, and by an ordinary window a resident won’t feel the difference. It appears in three places: whether there is somewhere to put the unit, what happens to the output at a low supply, and whether the floor can still be touched.

Where they really differ

CriterionIn-floor convectorRadiator
Floor-to-ceiling glazingThe casing lies in the screed under the glass, grille on topThere is no wall under the glass, nowhere to hang it
AppearanceOnly the grille is visibleThe device is on the wall
InstallationSet into the screed at the design stageHung at any time
Cold from the glassA curtain along the glass, if the length is close to its widthHeats where it hangs
Finished floorToo late: the screed can’t be redoneCan be installed
Low supply, 45/35Output without a fan drops threefoldAlso drops: the physics is the same

When a radiator is the right choice

An ordinary window with a sill, the renovation is done, nobody is going to raise the floor, the pipes are easily run to the wall. In this case a radiator does the same job more simply, and we won’t talk you into an in-floor convector. There’s also an argument in its favour: a radiator gives off part of its heat as radiation, and this is felt when a person sits nearby for a long time.

Floor-to-ceiling glass, but the screed is already poured

A radiator is not the only option here. Carrera has a floor-standing FRH that is placed right in front of the glass, and a skirting BR along the wall. The principle is the same, a curtain along the glass, but the floor doesn’t need to be opened up.

DeviceWidth × height, mmW per 1000 mm, 45/35
M/C 65, in the screed230 × 6582
S/C 90, in the screed230 × 90101
FRH, on the floor148 × 175123
FR2H, on the floor290 × 175169
BR 18, skirting60 × 18077
BR 21, skirting60 × 21097

All of this is natural convection. One mode is taken, 45/35, because in our tables in-floor units are given for 85/75 and 65/55, while floor-standing and skirting ones for 90/70 and 70/50: the “per metre” catalogue figures can’t be placed side by side. At 45/35 the spread is 77–169 W, so the type is chosen by location and appearance, and the output is matched by length.

Where people go wrong and when a convector is not suitable

  • A catalogue figure instead of the mode. S/C 90, 2000 mm long, without a fan gives 770 W at 85/75, 513 W at 65/55 and 256 W at 45/35. A heat pump usually runs at 45/35, so the 45/35 row is taken for it: a version with a fan (SV 90 at 30% speed gives 569 W here) or a longer unit. A radiator isn’t saved from this arithmetic either; in more detail in the review of a convector on a heat pump.
  • A decision after the screed is poured. A casing can’t be laid in a finished floor: what remains is FRH, BR or a radiator.
  • A thin screed. The lowest casing is 65 mm. If the depth is less, there is no in-floor series for you.
  • Heating is turned on infrequently. For an office or a shop, what matters is the speed of reaching the mode, not the sill; this is a separate review for an irregular schedule.

What to check before deciding

  • What is under the glass: a pier or the floor. Measure the height from the floor to the bottom of the glass.
  • The screed: poured or not, and what depth exactly under the glass, not in the middle of the room.
  • Supply and return in writing for the coldest day: 85/75, 65/55 or 45/35.
  • The output is taken from the row for your mode, not from the top catalogue figure.
  • For a version with a fan: a 24 V line and space for the power supply and thermostat.
  • The order of magnitude is given by the output calculator; the final selection is confirmed by an engineer.
Can a radiator be placed under a panoramic window?

Yes, if there is a pier under the glass: the radiator is hung on it. When the glass goes to the floor, there is no pier, and what remains is a convector in the screed or FRH or BR in front of the glass.

Is an in-floor convector needed if the heating is on a heat pump?

What’s needed is not a specific device but the table row for 45/35. S/C 90 at 2000 mm without a fan gives 256 W there versus 770 W at 85/75, so for a heat pump a version with a fan or extra length is taken.

Can a convector be added to a finished renovation?

An in-floor one, no: it needs a screed. FRH and BR are placed on a finished covering, which won’t have to be opened up.

Does a convector make noise compared with a radiator?

Natural convection is silent. A fan makes noise: SV 90 at 30% speed gives 19.8–24.3 dB, at 100% up to 46.0 dB (range by lengths 1000–3000 mm).